S3300 60 TO 200KVA

 High Reliability

  • Wide input voltage and frequency range with high grid adaptability and prolong battery life.
  • Separate internal air channel which hot air drives directly towards heat sink without distressing the PCB’s and other internal sensitive components, improving the components service life and UPS reliability
  • High overload capacity on inverter and bypass
  • The most advanced and dual DSP control prevents single failure point and increase performance.
  • Intelligent fan control and redundant design: 15% load can be driven when 2 fans fail and 40% load when 1 fan fails
  • Integrated with input, output, bypass breaker and manual bypass switch for better protection of system.
  • All-round conformal coating to all PCB boards, protect electronics from environmental affection and corrosion.
  • Standard dust filter protect UPS placed in dusty environment.
  • High short circuit capacity with time duration settable from 20~200ms which provide high protection for system.
  • Cold start function which allow UPS start on battery when grid isn’t available.
  • Bus synchronization control function provides reliable high power for dual bus application
  • Power walk in function decrease the inrush to mains or generator.
  • Start-up delay function, to sequentially restart the rectifiers once the mains power supply is restored if there are several UPS within the overall system
  • No derating operates up to 40°C and continuously running under high ambient temperature up to 50°C with auto-derating.

Green Power

  • Advanced IGBT and three level technology, Low harmonic, high efficiency, effectively energy-saving.
  • High power density design, which small footprint on 100KW only 0.38m² for saving installation space.
  • High input power factor up to 0.99 and low Input THDi: < 3.0% at full load, much less grid pollution and costs
  • AC/AC efficiency up to 96.5% and 30% load up to 95% efficiency reduces heat dissipation and limits power consumption costs
  • ECO mode efficiency up to 99.2% lead to significant cost reduction
  • W-ECO mode could reach 98.5% efficiency, THDi below 5% and transfer time below 4ms to reduce TCO.
  • Self-load test function, easy debugging and easy onsite test during commissioning, before it is connected the real load, without using costly temporary loads, cabling and breakers for energy saving.
  • Parallel ECO mode maximum whole system efficiency.
  • Intelligent sleep mode which UPS sleep in random keep maximum efficiency and energy saving.
  • 8 units of intelligent paralleling helps to achieve maximum capacity up to 1.6MW.

Intelligent Management

  • Fault Trace Management (FTM) for convenient failure analysis (waveform record before & after of the fault point for 200ms) which easily figure out faulty point.
  • 3 stage battery charging prolong the service life of batteries
  • Intelligent battery management and multiple setting, ±14~±24 pcs batteries per string allow customers to get the faulty battery out instead of replacing it
  • Key components pre-alarm function which precaution the system fault and remind service for key components, like capacitor, fan.
  • Full asset management record the spare parts replacement, timeline and service people.
  • Cabinet temperature detect and pre-notification which prevent over temperature.
  • Smart programmable dry contact which have 5 input dry contact and 3 output dry contact, which input dry contact have more than 10 functions and output dry contact have 18 functions allows to settable at site.
  • Smart generator mode which allow UPS sent signal to turn on and off generator, also taking part power from battery to compensation generator capacity.
  • Self-deducting function which save the preventive service time.
  • Common battery bank on parallel mode.
  • Frequency converter function (60Hz to 50Hz or 50Hz to 60Hz)
  • VRLA and Lithium battery compatible design

User-friendly Interface

  • User-friendly double physical ON/OFF button design to avoid false operation.
  • User-friendly graphical interface with Single-line mimic diagram showing system status.
  • Colourful 4.3″ and 7″ touch screen with LED Indicators ensure comprehensive and visualized information display.
  • Multicolour LED bar allowing quick and easy detection of the system status and simplified troubleshooting.
  • Multi-language build-in display with English, French, Spanish, Italian, Polish, Russian, Korean, Chinese.
  • High security access with separate password levels for users, technician and service engineers
  • Large data storage capacity 10,000pcs events logs.
  • Support firmware online update, one time update for touch screen, power unit, bypass unit and extended card.
  • Main unit display allows checking the information of each UPS status during parallel mode.

Technical Specifications

Model

S3300

Capacity (KVA)

60

80

100

120

160

200

Input

Voltage (Vac)

380/400/415 (138~485 L-L)

Frequency (Hz)

40~70

Power Factor

≥0.99

Phase

3φ4W+PE

THDi

≤2% (linear load, full load); ≤3% (nonlinear load, full load)

Bypass

Bypass Voltage (Vac)

380/400/415: -20%~+15%

Frequency Range (Hz)

50/60(±5%/±10%)

Overload

≤130%: long run; 131%-150%: 5min; 151%-200%: 1s; 201%-300%: 100ms; >300%: protect immediately.

Output

Capacity (kW)

60

80

100

120

160

200

Power Factor

1 (0.5 leading to 0.5 lagging)

Voltage (Vac)

380/400/415±1%

Frequency (Hz)

50/60±0.1% (Battery mode)

Phase

3φ4W+PE

Three Phase Difference

≤1%

THDv with 100% load

<1% at linear load, <3% at non-linear load

Transfer Time (ms)

0

AC-AC Efficiency

up to 96.5%

Overload*

≤105%:Long run; 106%-110% load: 60 mins, 111%-125% load: 10 mins, 126%-150% load:1 min, >150% load: 200ms

Battery

Battery Voltage (Vdc)*

±192(±168 ~±288 adjustable)

±192(±168 ~±288 adjustable)

BATT Type

External

Charging Current (A) MAX*

30

60

General

Communication Interface

RS485, MODBUS, dry contact(RS232, BMS,SNMP, expend dry contact card are optional in slot)

Display

4.3-inch Touch screen+LED+LED bar

7-inch touch screen+LED+LED bar

Alarm

AC input abnormal, low battery, overload, failure

Protection

Output short-circuit, overload, over-temperature, battery low voltage, output over/low voltage

Noise (dB)

<65

Altitude(m)

0-2000 no derate. 2000-3000 m derate power by 1 % per each 100 m increase

Protection Degree

20

Operating Temperature (°C)

0 ~ 40 no derate,40~50 auto derate.

Relative Humidity

0 ~ 95%, no condensation

Dimension (W×D×H)(mm)

400×960×1200

600×1000×1600

Weight (kg)

145

159

161

163

310

312

 

  • Specification is subject to change without prior notice.
  • * Condition comply

More Options

  • SNMP Communication card
  • Expanded dry contact kit (4 in 4 out)
  • BMS kit for lithium battery communication
  • Intelligent Battery Monitoring System
  • Battery tripping kit
  • N+X in parallel
  • Input and output isolation transformer
  • Battery Charge Temperature Compensation
>