S3300 Plus 60 TO 200KVA

Exceptional Performance And Efficiency

Highlights

  • Complete range 60-200 KVA.
  • Small footprint.
  • High efficiency up to 96.5%.
  • Zero impact.
  • Flexibility of use.
  • Advanced communications.

The S3300 Plus series is ideal for protecting data centers and telecommunications systems, IT networks and critical systems in general, where the risks connected with poor energy supply can compromise the continuity of activities and services.

The S3300 Plus series is available in 60-80-100-125-160-200 kVA models with three-phase input and output and ON LINE double conversion technology in accordance with VFI-SS-111 classification (as set out in standard IEC EN 62040-3).

S3300 Plus is designed and built using state-of-the-art technology and components. It has a fully controlled IGBT rectifier to minimize the impact on the grid. It is controlled by a DSP (Digital Signal Processor) microprocessor to provide maximum protection to the powered loads with no impact on downstream systems, and optimized energy savings.

Zero Impact Source

S3300 Plus solves installation problems in systems where the power supply has limited power available, where the UPS is supported by a generator or where there are compatibility problems with loads that generate harmonic currents; S3300 has a zero impact on its power source, whether this is the mains power supply or a generator:

  • Input current distortion <2.5%.
  • Input power factor 0.99.
  • Power walk-in function that ensures progressive rectifier start up.
  • Start-up delay function, to restart the rectifiers when mains power is restored if there are several UPS in the system.

In addition, S3300 Plus plays a filtering and power factor correction role in the power network upstream of the UPS, as it eliminates harmonic components and reactive power generated by the power utilities.

High Efficiency

State-of-the-art three-level NPC inverters are used across the power range (60-200 kVA) to achieve an operating efficiency of 96.5%.

These technology halves (50%) the energy dissipated in a year by traditional UPS, with an efficiency level of 92%. Its exceptional performance makes it possible to recover the capital investment cost in less than three years of operation.

Battery Care System

Proper battery care is critical to ensuring correct UPS operation in emergency conditions. The SATRON UPS battery care system consists of a series of features and capabilities to optimize battery management and obtain the best performance and operating life possible.

Battery recharging: S3300 Plus is suitable for use with hermetically sealed lead-acid (VRLA), AGM and GEL batteries and Open Vent and Nickel Cadmium batteries. Depending on the battery type, different charging methods are available:

  • One-level voltage recharge typically used for widely available VRLA AGM batteries.
  • Two-level voltage recharge according to IU specification.
  • Charge blocking system to reduce electrolyte consumption and lengthen the life of VRLA batteries.

Recharge voltage compensation based on temperature in order to prevent excessive battery charges or overheating.

Battery tests to diagnose in advance any reduction in performance or problems with the batteries.

Deep discharge protection: during extended low-load discharges, the end- of-discharge voltage is increased – as recommended by battery manufacturers – to prevent damage or reduced battery performance.

Ripple current: recharge ripple current (residual AC component) is one of the main causes of reduced reliability and battery life.

Using a high frequency battery charger, S3300 reduces this value to negligible levels, prolonging battery life and maintaining high performance over a long period of time.

Wide voltage range: the rectifier is designed to operate within a wide input voltage range (up to -40% at half load), reducing the need for battery discharge and thus helping to extend battery life.

Maximum Reliability And Availability

Distributed parallel configuration of up to 8 units per redundant (N+1) or power parallel system.

The UPS continue to operate in parallel even if the connection cable is interrupted (Closed Loop).

Low Running Costs

A combination of advanced technology high performance components allows S3300 Plus to provide exceptional performance and efficiency:

  • The type of input stage (IGBT rectifier) ensures an input power factor close to 1 with low current distortion, avoiding the need for bulky and expensive filters.
  • Unity output power factor for MST 160-200 make it suitable to any data center application ensuring full power availability no matter what the utilities power factor range (typically from 0.9 lagging to 0.9 leading).
  • More active power than a traditional UPS, guaranteeing a greater margin when sizing UPS for potential future load increases.
  • Smart ventilation principle on S3300 Plus 160- 200 manages the number of operating fans and their speed according to room temperature and load level. This preserves the life span of the fans and at the same time we reduce noise level and overall power consumption for unnecessary UPS ventilation.

 

 

Flexibility

 

With its flexible configuration, performance, accessories and options, S3300 Plus is suitable for use in a wide range of applications:

  • Suitable for powering capacitive loads, such as blade servers, without any reduction in active power from 0.9 lead to 0.9 lag
  • ON LINE, ECO, SMART ACTIVE and STANDBY OFF operating Modes – compatible with centralized power systems (CSS) applications.
  • Frequency Converter Mode.
  • Configurable Energy Share sockets to preserve runtime for the most critical loads or to be activated only when mains power fails.
  • Cold Start to switch on the UPS even when there is no mains power present.
  • Optional temperature sensor for external battery cabinets, to assist recharge voltage compensation.
  • High power battery chargers to optimize charge time in the event of long runtimes.
  • Optional dual input mains power supply.
  • Isolation transformers for modifying he neutral earthing (separate power sources), or for galvanic isolation between the input and output.
  • Different sized battery cabinets and capacities, for extended runtimes.
  • With the S3300 60-100 the UPS can be raised up to 25 cm from the ground to allow the cables to pass more freely to/ from the UPS terminal board.

S3300 Plus 160-200 could be equipped with a side mounted top entry cabinet to arrange UPS cabling from the top.

Advanced Communications

S3300 Plus is equipped with backlit graphic display (240×128 pixels) providing UPS information, measurements, operating states and alarms in different languages.

It can also display waveforms and voltage/current forms.

The default screen displays UPS status, graphically indicating the status of the various assemblies (rectifier, batteries, inverter, bypass).

  • Advanced multi-platform communications for all operating systems and network environments:
  • PowerShield3 monitoring and shutdown software included for Windows operating systems 10, 8, 7, Hyper-V, 2019, 2016, 2012, and previous versions, Mac OS X, Linux, VMWare ESXi, Citrix XenServer and other Unix operating systems.
  • Compatible with SATRON Connect (remote monitoring service).
  • RS232 serial and USB ports.
  • 3 slots for the installation of optional communications accessories such as network adapters, potential free contacts, etc.
  • REPO Remote Emergency Power Off for switching off the UPS via a remote emergency button.
  • Input for the connection of the auxiliary contact of an external manual bypass.
  • Input for synchronisation from an external source.
  • Graphic display panel for remote connection.

Option Softwares

PowerShield3/PowerNetGuard

Accessories

NETMAN 204/MULTICOM 302/MULTICOM 352/MULTICOM 372/MULTICOM 384/MULTICOM 411

MULTICOM 421/MULTI I-O/MULTIPANEL/MBB 125A (60 kVA only)/MBB 400 A 4P

Product Accessories

Battery temperature sensor/Powerful battery charger/Programmable relay board.

MULTICOM 392/IP rating IP31-IP42/ Socle Box for S3300 evo 60-100/Energy Share sockets.

Top cable entry for S3300 160-200/Eyebolts kit for S3300 evo 160-200.

Technical Specifications

Model

S3300 Plus

Capacity (KVA)

60

80

100

120

160

200

Input

Rated voltage [V]

380 / 400 / 415 three-phase + N

Rated frequency [Hz]

50 / 60

Voltage tolerance [V]

400 ±20% @ full load1

Frequency tolerance [Hz]

40 - 72

Power factor @ full load

0.99

Current distortion

THDI ≤3%

THDI ≤2.5%

Bypass

Rated voltage [V]

380 / 400 / 415 three-phase + N

Rated voltage [V]

3 + N

Voltage tolerance (Ph-N) [V]

180 / 264 (selectable)

Rated frequency [Hz]

50 or 60 (selectable

Frequency tolerance

±5% (selectable)

Bypass overload

125% for 60 min., 150% for 10 min.

Output

Nominal power [kVA]

60

80

100

120

160

200

Active power [kW]

54

72

90

112.5

160

200

Power factor

0.9

1

Number of phases

3801 / 400 / 415 three-phase + N (selectable

Rated voltage [V]

3801 / 400 / 415 three-phase + N (selectable

Rated frequency [Hz]

50 or 60

Frequency stability on battery operation

0.01%

Voltage stability

±1%

Voltage distortion

<1% with resistive linear load / ≤3% with non-linear load

Crest factor [lpeack/lrms]

3:1

Static variation

±1%

Dynamic variation

±3%

Batteries

Type

VRLA AGM/GEL/NiCd/Li-ion/SuperCaps

Recharging method

One level, Two level, Cyclic recharge (selectable

Number of battery cells @ 2V

120+120

Battery arrangement

20+20 blocks (@ 12V) with Neutral central point

Recharge time

5h

Overall Specifications

Weight without batteries [kg

190

200

220

250

450

460

Dimensions (WxDxH) [mm]

500x830x1600

650x830

x1600

840x1035x1900

Communications

3 slots for communications interface / USB / RS232

Ambient temperature

0 °C - +40 °C

Battery Temperature

+20 °C - +25 °C

Range of relative humidity

5-95% non-condensing

Colour

RAL 7016 Anthracite grey

Protection Degree

P20

Noise level at 1 m [dBA ±2]

<63

<50

SMART ACTIVE efficiency

up to 99%

Standards

European directives: L V 2014/35/EU low voltage Directive EMC 2014/30/EU electromagnetic compatibility

Directive Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant

Classification in accordance with IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111

Moving the UPS

castors (60 - 200 kVA)

 

>