Exceptional Performance And Efficiency
Highlights
The S3300 Plus series is ideal for protecting data centers and telecommunications systems, IT networks and critical systems in general, where the risks connected with poor energy supply can compromise the continuity of activities and services.
The S3300 Plus series is available in 60-80-100-125-160-200 kVA models with three-phase input and output and ON LINE double conversion technology in accordance with VFI-SS-111 classification (as set out in standard IEC EN 62040-3).
S3300 Plus is designed and built using state-of-the-art technology and components. It has a fully controlled IGBT rectifier to minimize the impact on the grid. It is controlled by a DSP (Digital Signal Processor) microprocessor to provide maximum protection to the powered loads with no impact on downstream systems, and optimized energy savings.
Zero Impact Source
S3300 Plus solves installation problems in systems where the power supply has limited power available, where the UPS is supported by a generator or where there are compatibility problems with loads that generate harmonic currents; S3300 has a zero impact on its power source, whether this is the mains power supply or a generator:
In addition, S3300 Plus plays a filtering and power factor correction role in the power network upstream of the UPS, as it eliminates harmonic components and reactive power generated by the power utilities.
High Efficiency
State-of-the-art three-level NPC inverters are used across the power range (60-200 kVA) to achieve an operating efficiency of 96.5%.
These technology halves (50%) the energy dissipated in a year by traditional UPS, with an efficiency level of 92%. Its exceptional performance makes it possible to recover the capital investment cost in less than three years of operation.
Battery Care System
Proper battery care is critical to ensuring correct UPS operation in emergency conditions. The SATRON UPS battery care system consists of a series of features and capabilities to optimize battery management and obtain the best performance and operating life possible.
Battery recharging: S3300 Plus is suitable for use with hermetically sealed lead-acid (VRLA), AGM and GEL batteries and Open Vent and Nickel Cadmium batteries. Depending on the battery type, different charging methods are available:
Recharge voltage compensation based on temperature in order to prevent excessive battery charges or overheating.
Battery tests to diagnose in advance any reduction in performance or problems with the batteries.
Deep discharge protection: during extended low-load discharges, the end- of-discharge voltage is increased – as recommended by battery manufacturers – to prevent damage or reduced battery performance.
Ripple current: recharge ripple current (residual AC component) is one of the main causes of reduced reliability and battery life.
Using a high frequency battery charger, S3300 reduces this value to negligible levels, prolonging battery life and maintaining high performance over a long period of time.
Wide voltage range: the rectifier is designed to operate within a wide input voltage range (up to -40% at half load), reducing the need for battery discharge and thus helping to extend battery life.
Maximum Reliability And Availability
Distributed parallel configuration of up to 8 units per redundant (N+1) or power parallel system.
The UPS continue to operate in parallel even if the connection cable is interrupted (Closed Loop).
Low Running Costs
A combination of advanced technology high performance components allows S3300 Plus to provide exceptional performance and efficiency:
Flexibility
With its flexible configuration, performance, accessories and options, S3300 Plus is suitable for use in a wide range of applications:
S3300 Plus 160-200 could be equipped with a side mounted top entry cabinet to arrange UPS cabling from the top.
Advanced Communications
S3300 Plus is equipped with backlit graphic display (240×128 pixels) providing UPS information, measurements, operating states and alarms in different languages.
It can also display waveforms and voltage/current forms.
The default screen displays UPS status, graphically indicating the status of the various assemblies (rectifier, batteries, inverter, bypass).
Option Softwares
PowerShield3/PowerNetGuard
Accessories
NETMAN 204/MULTICOM 302/MULTICOM 352/MULTICOM 372/MULTICOM 384/MULTICOM 411
MULTICOM 421/MULTI I-O/MULTIPANEL/MBB 125A (60 kVA only)/MBB 400 A 4P
Product Accessories
Battery temperature sensor/Powerful battery charger/Programmable relay board.
MULTICOM 392/IP rating IP31-IP42/ Socle Box for S3300 evo 60-100/Energy Share sockets.
Top cable entry for S3300 160-200/Eyebolts kit for S3300 evo 160-200.
Technical Specifications
Model |
S3300 Plus |
|||||||||||||||||
Capacity (KVA) |
60 |
80 |
100 |
120 |
160 |
200 |
||||||||||||
Input |
||||||||||||||||||
Rated voltage [V] |
380 / 400 / 415 three-phase + N |
|||||||||||||||||
Rated frequency [Hz] |
50 / 60 |
|||||||||||||||||
Voltage tolerance [V] |
400 ±20% @ full load1 |
|||||||||||||||||
Frequency tolerance [Hz] |
40 - 72 |
|||||||||||||||||
Power factor @ full load |
0.99 |
|||||||||||||||||
Current distortion |
THDI ≤3% |
THDI ≤2.5% |
||||||||||||||||
Bypass |
||||||||||||||||||
Rated voltage [V] |
380 / 400 / 415 three-phase + N |
|||||||||||||||||
Rated voltage [V] |
3 + N |
|||||||||||||||||
Voltage tolerance (Ph-N) [V] |
180 / 264 (selectable) |
|||||||||||||||||
Rated frequency [Hz] |
50 or 60 (selectable |
|||||||||||||||||
Frequency tolerance |
±5% (selectable) |
|||||||||||||||||
Bypass overload |
125% for 60 min., 150% for 10 min. |
|||||||||||||||||
Output |
||||||||||||||||||
Nominal power [kVA] |
60 |
80 |
100 |
120 |
160 |
200 |
||||||||||||
Active power [kW] |
54 |
72 |
90 |
112.5 |
160 |
200 |
||||||||||||
Power factor |
0.9 |
1 |
||||||||||||||||
Number of phases |
3801 / 400 / 415 three-phase + N (selectable |
|||||||||||||||||
Rated voltage [V] |
3801 / 400 / 415 three-phase + N (selectable |
|||||||||||||||||
Rated frequency [Hz] |
50 or 60 |
|||||||||||||||||
Frequency stability on battery operation |
0.01% |
|||||||||||||||||
Voltage stability |
±1% |
|||||||||||||||||
Voltage distortion |
<1% with resistive linear load / ≤3% with non-linear load |
|||||||||||||||||
Crest factor [lpeack/lrms] |
3:1 |
|||||||||||||||||
Static variation |
±1% |
|||||||||||||||||
Dynamic variation |
±3% |
|||||||||||||||||
Batteries |
||||||||||||||||||
Type |
VRLA AGM/GEL/NiCd/Li-ion/SuperCaps |
|||||||||||||||||
Recharging method |
One level, Two level, Cyclic recharge (selectable |
|||||||||||||||||
Number of battery cells @ 2V |
120+120 |
|||||||||||||||||
Battery arrangement |
20+20 blocks (@ 12V) with Neutral central point |
|||||||||||||||||
Recharge time |
5h |
|||||||||||||||||
Overall Specifications |
||||||||||||||||||
Weight without batteries [kg |
190 |
200 |
220 |
250 |
450 |
460 |
||||||||||||
Dimensions (WxDxH) [mm] |
500x830x1600 |
650x830 x1600 |
840x1035x1900 |
|||||||||||||||
Communications |
3 slots for communications interface / USB / RS232 |
|||||||||||||||||
Ambient temperature |
0 °C - +40 °C |
|||||||||||||||||
Battery Temperature |
+20 °C - +25 °C |
|||||||||||||||||
Range of relative humidity |
5-95% non-condensing |
|||||||||||||||||
Colour |
RAL 7016 Anthracite grey |
|||||||||||||||||
Protection Degree |
P20 |
|||||||||||||||||
Noise level at 1 m [dBA ±2] |
<63 |
<50 |
||||||||||||||||
SMART ACTIVE efficiency |
up to 99% |
|||||||||||||||||
Standards |
European directives: L V 2014/35/EU low voltage Directive EMC 2014/30/EU electromagnetic compatibility Directive Standards: Safety IEC EN 62040-1; EMC IEC EN 62040-2; RoHS compliant Classification in accordance with IEC 62040-3 (Voltage Frequency Independent) VFI - SS - 111 |
|||||||||||||||||
Moving the UPS |
castors (60 - 200 kVA) |